Will a generator run a pellet stove?

Updated 2026-11-23

This page contains affiliate links. Specs come from manufacturer data; we did not lab-test these products (how we work). Last verified 2026-11-23.

Short answer

Yes, a pellet stove draws 125 W running and 310 W during the 10 to 12 minute igniter phase, so a 1,800 W inverter generator has more than ten times the capacity it needs. A 1,024 Wh power station runs it for about 7 hours.

Yes. A pellet stove is one of the smallest loads you can put on a generator. It draws 125 watts while it runs and 310 watts while the igniter is heating pellets, and that higher number lasts only about 10 to 12 minutes. Any 1,800 watt inverter generator has more than ten times the running capacity the stove needs. The real question is usually the rest of the house, and how long you want to go between refueling.

The igniter is the only spike, and it is not a motor surge

In plain terms, 125 watts is about two old 60 watt light bulbs. That covers the auger, the room fan, the exhaust fan, and the control board. The igniter adds another 185 watts, so the stove pulls 310 watts, roughly five bulbs, while it lights the fire.

The igniter works like a toaster element or a diesel glow plug. It is a heating element, not a motor, so there is no split second inrush. The stove sits at 310 watts for 10 to 12 minutes, then the control board shuts the igniter off and the draw drops to 125 watts. That is why you size for the igniter number, not just the running number.

Why the stove stops when the power does

A pellet stove is not a wood stove. It needs electricity to feed pellets, pull air through the fire, and push exhaust out the vent. Cut the power and the auger stops, so no new fuel arrives, but the fire in the burn pot still has fuel and heat. Without the exhaust fan, the burn starves for air and goes dirty. Smoke can back up into the room instead of going up the vent, especially if the door gasket is worn or the venting drafts poorly.

When power returns, a pot of unburned pellets can light off with a hard puff. Some manuals call for a shutdown cycle: the fan keeps running until the fire is out, and pulling the plug skips that. Read your stove’s manual for its shutdown and restart procedure, because stoves differ. This is general safety, not a diagnosis of your unit.

If the stove has been running and the power fails, do not open the door to look. Wait for the smoke to clear. Keep a CO alarm on every level, and treat smoke in the room as a reason to ventilate and get out.

Inverter generators that pass, with room to spare

The stove needs 157 watts of rated running capacity by our rule (125 ÷ 0.8, rounded up) and 310 watts of peak. Here is how a few inverter models in our data compare.

Model Rated running / starting 80% continuous limit Verdict
Honda EU2200i 1,800 / 2,200 W 1,440 W Yes
Westinghouse iGen2200c 1,800 / 2,200 W 1,440 W Yes
Champion 2500W Dual Fuel Inverter 1,850 / 2,500 W 1,480 W Yes
Champion 4500W Electric Start Dual Fuel Inverter 3,500 / 4,500 W 2,800 W Yes

Every one carries the stove at a small fraction of its capacity. The Honda EU2200i uses about 9 percent of its 1,440 watt continuous limit while the stove runs. Even the Champion 2500W Dual Fuel Inverter, which drops to 1,665 watts running on propane for a 1,332 watt continuous limit, is far above the 157 watts the stove asks for.

Do not buy a generator for the stove. Buy it for the fridge, the lights, and whatever else you want during the storm, then check that the stove fits, which the sizing guide walks through. It almost always will.

Power stations: hours per charge

A power station is a better match for a stove you want to run quietly overnight, as long as it covers the igniter and has enough watt-hours. Our runtime rule is battery watt-hours × 0.85 inverter efficiency ÷ average draw. With a duty cycle of 1, the average draw is the full 125 watts.

For the EcoFlow DELTA 3: 1,024 Wh × 0.85 = 870.4 Wh, and 870.4 ÷ 125 = 7.0 hours.

Model Battery Rated running / starting Continuous limit Hours at 125 W
Jackery Explorer 300 v2 288 Wh 300 / 600 W 240 W 2.0
EcoFlow DELTA 3 1,024 Wh 1,800 / 3,600 W 1,440 W 7.0
BLUETTI AC180 1,152 Wh 1,800 / 2,700 W 1,440 W 7.8
Jackery Explorer 1500 v2 1,536 Wh 2,000 / 4,000 W 1,600 W 10.4
Anker SOLIX C2000 Gen 2 2,048 Wh 2,400 / 4,000 W 1,920 W 13.9

The Explorer 300 v2 has 600 watts of surge, which covers the 310 watt igniter, but its 300 watt continuous rating sits just below 310 watts. The math passes it on surge alone, yet a stove you light every evening deserves a unit rated above 310 watts continuous. The other four have plenty of headroom.

Pick a station with pure sine wave output, the cleaner match for a stove control board. A modified sine wave inverter may confuse the board, so confirm it in the manual.

Worked example: stove, fridge, and lights

Mike’s list is the stove, the refrigerator, and ten LED bulbs.

  • Pellet stove: 125 W running, 310 W starting
  • Refrigerator: 700 W running, 2,200 W starting
  • LED lights: 100 W running, no surge

Add the running watts: 125 + 700 + 100 = 925 watts.

Divide by 0.8 for the smallest rated running capacity: 925 ÷ 0.8 = 1,156.25, which rounds up to 1,157 watts.

Now the peak. The stove adds 185 watts above its running draw, the fridge adds 1,500, and the lights add nothing. Peak = 925 + 1,500 = 2,425 watts.

So the list needs at least 1,157 watts running and 2,425 watts of surge. Here is how the generators land:

Model Running vs 1,157 W Surge vs 2,425 W Verdict
Honda EU2200i 1,800 W, clears 2,200 W, 225 short No
Champion 2500W Dual Fuel 1,850 W, clears 2,500 W, 75 to spare Marginal
Champion 4500W Dual Fuel 3,500 W, clears 4,500 W, clears Yes

The stove alone needs 157 watts. All three need 1,157 watts running and 2,425 watts at the fridge’s startup, so the refrigerator pushes the size up, not the stove.

A 2,200 watt unit can run the stove and lights, or the fridge by itself at the edge of its surge rating, but not all three when the compressor starts. For that class, put the stove on a power station and let the generator carry the fridge and lights. One small generator cannot do it all.

What about a tank of gas overnight?

The Honda EU2200i lists 8.1 hours at one quarter load on its 0.95 gallon tank. One quarter of 1,800 watts is 450 watts, more than three times the stove’s draw, so that figure is a floor for this load, not a ceiling.

If fuel scaled perfectly with load, 0.95 ÷ 8.1 = 0.117 gallons per hour at 450 watts. At 125 watts that becomes 0.117 × (125 ÷ 450) = 0.033 gallons per hour, or about 29 hours per tank. Treat it as an estimate: small engines burn fuel at idle too, so the real number is lower. Even so, one tank should cover a night and most of the next day.

Refuel only after the generator cools, and do it outside. Store gasoline in an approved container, away from the house and ignition sources.

Size the rest of the house

Put your list into the wattage calculator. Enter the stove at 125 watts running and 310 watts starting, add the fridge and lights, and compare the result against a generator or power station.

Sources for the numbers on this page

Appliance wattage

  • Pellet stove: US Stove AP5710 manual: 125 W operational, 310 W igniter running; the igniter stays on for at least 10 and up to 12 minutes during ignition, so starting_w is the igniter-phase draw (usstove.com)
  • Refrigerator: chart lists 700 running / 2200 starting (Refrigerator or Freezer) (powerequipment.honda.ca)
  • LED lights (10 bulbs): LED lights 8–15 per bulb; 10 bulbs ≈ 80–150 running; no starting surge (championpowerequipment.com)

Model specs (manufacturer pages)

Retrieved when the page was last verified. Makers update spec pages; if a figure changed, tell us and we will correct it.

Safety

Always run a gas or dual-fuel generator outdoors, at least 20 feet from doors, windows, and vents, with the exhaust pointed away from the house. Install a CO alarm and never backfeed your home's wiring.